How to Unlock My Honeywell Oil Heater R7184b1032

Save

The R7184b1032 is an interrupted electric-oil primary control manufactured by Honeywell. R7184 series primary controls can be found in oil-fired furnaces and boilers from a variety of manufacturers, including Nordyne and New Yorker. The controls have a restricted lockout safety feature that shuts off the oil heater when flame is detected during the valve-on delay -- or if it isn't detected during the trial for ignition. You can unlock a Honeywell R7184b1032 oil-heater primary control in less than a minute.

  • Watch the LED on the primary control to confirm it's in restricted lockout mode; if the control is locked out, the light will flash on and off every half second.

  • Locate the red "Reset" button on the side of the primary control. Press and hold the button for 30 seconds, or until the LED flashes twice.

  • Look at the LED; a single, one-second flash indicates that the control was unlocked successfully and has returned to Standby mode.

Tips & Warnings

  • To reset a simple malfunction, press and release the red "Reset" button on the side of the primary control.
  • Pressing the "Reset" button repeatedly pumps excess oil into the combustion chamber and creates a fire hazard when the burner lights.