How to Size an Overcurrent Device for a Transformer

Transformers are at the heart of power distribution systems
••• Jupiterimages/Photos.com/Getty Images

Circuit breakers protect transformers from overcurrent situations and short circuits. They also protect circuits downstream from the transformer. Once the circuit breaker opens or "trips" due to a short circuit or some other overcurrent scenario, the circuit breaker blocks current flow to the circuit. Technicians must physically reset the breaker to allow the circuit to function normally. Circuit breakers are sized in amps; meaning once the overcurrent scenario reaches that current value, the circuit breaker will trip.

Size the Primary Side of the Transformer.

    Find the rated kilovolt-amperes or "KVA" of the transformer. Refer to transformer specifications. As a example, assume 20 KVA.

    Find the primary voltage of the transformer or "Vprimary." Refer to transformer specifications. As an example, assume the primary voltage is 480-volts.

    Calculate the primary current flow, or "Iprimary," using the formula Iprimary = KVA x 1000/Vprimary.

    Using the example numbers:

    Iprimary = (20 x 1000)/480 = 20,000/480 = 41.6 amps.

    Note: If you had a 3-phase transformer, the formula would be Iprimary = KVA x 1000/(Vprimary x 1.732). The 1.732 accounts for the 3-phase configuration.

    Find the circuit breaker size for the primary side of the transformer by multiplying Iprimary by 1.25.

    Continuing with the example:

    Primary circuit breaker size = 41.6 x 1.25 = 52 amps

Size the Secondary Side of the Transformer.

    Find the secondary voltage of the transformer or "Vsecondary." Refer to transformer specifications. As an example, assume the secondary voltage is 240-volts:

    Calculate the secondary current flow, or "Isecondary," using the formula Isecondary = KVA x 1000/Vsecondary.

    Using the example numbers:

    Isecondary = (20 x 1000)/240= 20,000/240 = 83.3 amps.

    Note: If you had a 3-phase transformer, the formula would be Isecondary = KVA x 1000/(Vsecondary x 1.732). The 1.732 accounts for the 3-phase configuration.

    Find the circuit breaker size for the secondary by multiplying Isecondary by 1.25.

    Continuing with the example:

    Secondary circuit breaker size = 83.3 x 1.25 = 104 amps.

Related Articles

Circuit Breaker Requirements for a 7.5 HP Air Compressor
How to Calculate CT Ratio
How to Calculate 30 KW to Amps
How to Size a Transformer KVA
How to Calculate Electrical Transformer Output
How to Calculate Millivolts to Amps
How to Calculate 3-Phase Line-To-Ground Voltage
How to Calculate Cost of Electricity for Electric Motor...
How to Calculate Toroidal Transformers
How to Calculate Kva to Amp
How to Connect Step-Up 3-Phase Transformers
How to Determine Current Capacity of Transformers
How to Calculate Transformer Turns Ratio
How to Calculate Transformer Primary Current
How to Calculate the Value for the Vce in a Transistor
How to Calculate Three Phase Amps From Megawatts
How to Calculate the Short Circuit Rating
How to Wire a Battery in Series
Circuit Breaker Requirements for a 7.5 HP Air Compressor
How to Change Electrical Amps to Watts